rivera coil manufacturing logo

Call Us

+91 424 2273399

Call Us

+91 97889 03399

Mail Us

info@rivera.co.in

Stator Diamond Coils

Electrical Routine Test

The electrical routine testing at different stages is performed with guidelines of IEEE/IEC/IS international standards. The High voltage test on individual coils and Stator winding is shall perform as per our below standard norms or customer specific requirement

S.noStage of testingElectrical TestResin Rich coilsVPI coilsHybrid Insulation
1
Test on Individual coils
Tan delta and capacitance measurement with guard electrodesThe tan delta measurement carried out from 0.2 VL to 1.2 VL insteps of 0.2 VLNAThe tan delta measurement carried out from 0.2 VL to 1.2 VL insteps of 0.2 VL
Inter turn Surge test(1.7 * VL) kV(1.7 * VL) kV(1.7 * VL) kV
Ac high voltage test in kV1.3 X ( 2 X VL + 1 )1.3 X VL1.3 X ( 2 X VL + 1 )
2
Test before stator connection ( after coils insertion in wound stator)
Insulation resistance testIR at 1 minute and 10 minuteIR at 1 minute and 10 minuteIR at 1 minute and 10 minute
Ac high voltage test in kV1.2 X ( 2 X VL + 1 )1.2 X VL1.2 X ( 2 X VL + 1 )
Insulation resistanceIR at 1 minuteIR at 1 minuteIR at 1 minute
Inter turn test – Surge in kV(1.6 * VL) kV(1.6 * VL) kV(1.6 * VL) kV
RTD’s high voltage a.cAt 1.5 kv for 5 secondsAt 1.5 kv for 5 secondsAt 1.5 kv for 5 seconds
RTD’s resistanceMeasure the resistance of all RTDMeasure the resistance of all RTDMeasure the resistance of all RTD
3
Test after stator connection with cables
Winding resistanceResistance per phases at room temperatureResistance per phases at room temperatureResistance per phases at room temperature
Insulation resistance testIR at 1 minute and 10 minuteIR at 1 minute and 10 minuteIR at 1 minute and 10 minute
Ac high voltage test in kV1.1 X ( 2 X VL + 1 )1.1 X VL1.1 X ( 2 X VL + 1 )
Insulation resistanceIR at 1 minuteIR at 1 minuteIR at 1 minute
Inter turn test – Surge in KvAt 2 kV (Comparison with phases)At 2 kV (Comparison with phases)At kV (Comparison phases)
Tan delta and capacitance measurementThe tan delta measurement carried out from 0.2 VL to 1.2 VL insteps of 0.2 VLNANA
RTD’s resistanceMeasure the resistance of all RTDMeasure the resistance of all RTDMeasure the resistance of all RTD
4
Test after stator VPI
(impregnation and post curing in hot chamber)
Winding resistance
NA
Resistance per phases at room temperatureResistance per phases at room temperature
Insulation resistance testIR at 1 minute and 10 minuteIR at 1 minute and 10 minute
Ac high voltage test in kV1. 05 X ( 2 X VL+ 1)1. 05 X ( 2 X VL + 1 )
Insulation resistanceIR at 1 minuteIR at 1 minute
Tan delta and capacitance measurementThe tan delta measurement carried out from 0.2 VL to 1.2 VL insteps of 0.2 VLThe tan delta measurement carried out from 0.2 VL to 1.2 VL insteps of 0.2 VL
RTD’s resistanceMeasure the resistance of all RTDMeasure the resistance of all RTD

Where VL is The rated line voltage of the stator coil. The IR test for individual coils can be performed, if required.

Acceptance Criteria:

  • Surge test – Rivera Standard Norms and IEC 60034-15  – Should not be short circuited between the turns and Windings
  • AC HV test – Rivera Standard Norms and IEC 60034 & BS 499-5000 – Should not be failure in slot portion at specified voltage for duration of 1 minute
  • Insulation Resistance (IR) and Polarization Index (PI) – IEEE 43 -2000 – The minimum value of IR 1 minute is 100 MΩ and PI 10/1minute is 2.5
  • Tan delta test – IEEE 286 -2000 & IEC 60034-27-3
  1. At 0.2 * Un Dissipation factor should < 2 %
  2. Tan delta dissipation factor per 0.2 * Un should < 0.5%
  3. Dissipation factor tip-up between 0.6 * Un and 0.2 * Un should < 0.5 %

Electrical type test and testing standards

There shall be no voltage breakdown at 1.5 * VL + 1 for 30 seconds duration, 10% of total coils/bars

A voltage of 2 Un + 1 KV shall be applied for 1 minute between coil terminals and earth. The applied voltage shall then be increased at the rate of 1 kV/s up to 2 * (2*VL+1) kV, and then immediately be reduced at the rate of at least 1 kV/s to zero. There shall be no voltage breakdown during this sequence.

Impulse voltage withstand test on sample coils at 0.65 * (4 Un + 5 kV) with rise time of 0.2µs+/-0.1µs for five switching operation. The coils must withstand the impulse voltage

The coils/bars temperature rise from 40°C to 150° C and cooling from 150°C to 40°C for 500 cycles. During TCT tapping test, Tan delta test and PD measurements shall be repeated after 50,100,250 and 500 cycles.
The Voltage endurance test shall be performed on the coils/bars with schedule B.

The slot portion of the coils and bars from high voltage withstand test cut into equal lengths, then microscopic investigation and measuring of insulation thickness shall be performed.

The surface resistance of coils/bars 500 ohms to 5000 ohms/square

Coils/bars line voltage6.6 kV11 kV13.2 kV13.8 kV15.75 kV
Test voltage in Schedule A (400Hours at 120°C)14.3 kV23.87 kV28.64 kV29.94 kV34.177 kV
Test Voltage in Schedule B
(200Hours at 120°C)
16.69 kV27.83 kV33.39 kV34.91 kV39.84 kV

 

The standards used for testing are